SURGE PROTECTION DEVICE

SURGE PROTECTION DEVICE

Surge protection device Mounting method: DIN rail (top hat rail) 35 mm With remote signalling contact: no Number of conductors (without earthing): 4 Construction size: 4 modular spacing Max. continuous voltage AC: 275 V. Nominal discharge surge current (8/20): 20 kA. Nominal voltage AC: 230 V. Category type 2: yes Voltage protection level L-N: 1.2 kV. Signalling at the device: Optic Max. continuous voltage DC: 350 V. Protection category: IP20 Voltage protection level N-PE: 1.2 kV. Integrated backup fuse: no System configuration DC: no System configuration IT: no System configuration TN: no System configuration TN-C: no System configuration TN-S: yes System configuration TT: no System configuration other: no System configuration TN-C-S: no Max. discharge surge current (8/20): 40 kA. Short-circuit breaking capacity (Isccr): 50 kA.

Produktkennzeichen

SKU: 7P2582750020
EAN: 8012823398150
GTIN: 8012823398150
MPN: 7P2582750020

Kategorien

Eigenschaften

Baugröße
4 TE
Montageart
Hutschiene TH35
Netzform DC
Nein
Netzform IT
Nein
Netzform TN
Nein
Netzform TT
Nein
Schutzpegel
-
Leckstromfrei
-
Netzform TN-C
Nein
Netzform TN-S
Ja
Schutzart (IP)
IP20
Nennspannung AC
230 V
Nennspannung DC
-
Netzform TN-C-S
Nein
Schutzpegel L-N
1.2 kV
Max. PV-Spannung
-
Schutzpegel N-PE
1.2 kV
Netzform sonstige
Nein
Prüfklasse Typ 2
Ja
Mit Fernmeldekontakt
Nein
Integrierte Vorsicherung
Nein
Signalisierung am Gerät
optisch
Höchste Dauerspannung AC
275 V
Höchste Dauerspannung DC
350 V
Nennableitstoßstrom (8/20)
20 kA
Max. Ableitstoßstrom (8/20)
40 kA
Anzahl der Leiter (ohne Erde)
4
Kurzschlussfestigkeit (Isccr)
50 kA
Integrierter Kurzschlussschutz
-
Max. Leiterquerschnitt flexibel (feindrähtig)
-
Max. Leiterquerschnitt starr (ein-/mehrdrähtig)
-
Integrierter Kurzschlussschutz selektiv zur Sicherung gG
-
Max. Überstromschutzeinrichtung V-Verdrahtung (Sicherung)
-
Max. Überstromschutzeinrichtung Stichverdrahtung (Sicherung)
160 A